EFFETS DU DEMARRAGE ANTICIPE DU VENTILATEUR DE LA BATTERIE EXTERIEURE SUR LES TRANSITIONS DE PRESSION, AU COURS DU DEGIVRAGE PAR INVERSION DE CYCLE D'UNE POMPE A CHALEUR.

EFFECTS OF OUTDOOR COIL FAN PRESTART ON PRESSURE TRANSIENTS DURING THE REVERSE CYCLE DEFROST OF A HEAT PUMP.

Auteurs : ANAND N. K.

Résumé

A LA FIN D'UNE PERIODE DE DEGIVRAGE TYPE, LE FRIGORIGENE A HAUTE PRESSION, DANS LA BATTERIE EXTERIEURE, EST EXPOSE A UNE CONDUITE D'ASPIRATION BASSE PRESSION DU COMPRESSEUR, ET LE FRIGORIGENE A BASSE PRESSION DANS LA BATTERIE INTERIEURE EST EXPOSE A UNE CONDUITE DE REFOULEMENT HAUTE PRESSION DU COMPRESSEUR. ON ASSISTE A UNE ELEVATION ET A UNE CHUTE SOUDAINES DE PRESSION DANS LA CONDUITE D'ASPIRATION DU COMPRESSEURAINSI QU'A UNE CHUTE ET ELEVATION SOUDAINES DE PRESSION DANS LA CONDUITE DE REFOULEMENT. DE TELLES TRANSITIONS DE PRESSION SOUMETTENT LE COMPRESSEUR ET LES CONDUITES DE FRIGORIGENE A UN CHOC MECANIQUE QUI DIMINUE LA FIABILITE. SI ON MET EN SERVICE LE VENTILATEUR DE LA BATTERIE EXTERIEURE AVANT LA FIN DU CYCLE DE DEGIVRAGE, LA BATTERIE EXTERIEURE EST REFROIDIE ET LES TRANSITIONS DE PRESSION A LA FIN DU DEGIVRAGE SONT REDUITES. LES RECHERCHES ONT MONTRE QU'UN DEMARRAGE ANTICIPE DE 20 SECONDES ETAIT IDEAL POUR REDUIRE LES TRANSITIONS DE PRESSION.

Détails

  • Titre original : EFFECTS OF OUTDOOR COIL FAN PRESTART ON PRESSURE TRANSIENTS DURING THE REVERSE CYCLE DEFROST OF A HEAT PUMP.
  • Identifiant de la fiche : 1991-0377
  • Langues : Anglais
  • Date d'édition : 1989
  • Source : Source : ASHRAE Trans.
    vol. 95; n. 2; 699-704; 9 fig.; 1 tabl.; 8 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.