Efficacité de DBNPA pour prévenir les infections dues à la Legionella pneumophila : résultats expérimentaux dans un modèle de circuit d'eau.

Efficacy of DBNPA against Legionella pneumophila: experimental results in a model water system.

Auteurs : GAO V., ZHOU P., LIN Y. E.

Résumé

Although chlorine is the best biocide for Legionella control, corrosion is a major disadvantage associated with its use. Nonoxidizing biocides have the advantage of reduced corrosion but may have marginal efficacy. DBNPA (2,2-dibromo-3-nitrilopropionamide) is a nonoxidizing biocide that has demonstrated short-term efficacy against Legionella after exposure to a single dose of 8-19 ppm, but dosing at these levels is not economically feasible. Therefore, the objective of the study was to compare the efficacy of 5.0 ppm and 15.0 ppm slug doses of DBNPA vs. 5.0 ppm and 1.0 ppm with multiple dosing to achieve a residual level of 1.0 ppm of DBNPA over a 16-day period.

Détails

  • Titre original : Efficacy of DBNPA against Legionella pneumophila: experimental results in a model water system.
  • Identifiant de la fiche : 2002-0945
  • Langues : Anglais
  • Source : ASHRAE Transactions. 2001 Winter Meeting, Atlanta, GA. Volume 107, part 1 + CD-ROM.
  • Date d'édition : 2001
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (60)
Voir le compte rendu de la conférence