Document IIF
Efficacité énergétique du circuit de refroidissement en fonction de la charge du précédent et du nouveau frigorigène alternatif.
Energetic efficiency of cooling circuit depending on the charge of the previous and new alternative refrigerant.
Numéro : pap. n. 209
Auteurs : ŠUSTEK J., TOMLEIN P.
Résumé
Energetic efficiency of cooling circuit influences the amount of refrigerant, which is changing when refrigerants with high GWP are substituted by refrigerants with low GWP. Substitution of R404A for R449A or R448A was carried on experimental cooling box with own cooling circuit and original refrigerant R404A with air cooled condenser. Heating load was selected adequately to cooling output of evaporator, which was possible to regulate by speed of ventilators. Cooling circuit was tested by ClimaCheck. Measured were 2 pressures, 9 temperatures humidity of surroundings and inside the box. Parameters were measured in real time in chosen interval. Measurements were carried out with increasing and with decreasing charge of refrigerant. Optimizing of refrigerant charge was carried out in the range of very low and very high refrigerant charge due to installed collector in the liquid line. Deciding parameters for the evaluation of energetic efficiency before and after refrigerant substitution were superheating and subcooling under stabile function of cooling circuit. Measurements proved different results with compared refrigerants and the need for adjusting of thermostatic expansion valve after the retrofit.
Documents disponibles
Format PDF
Pages : 8
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Energetic efficiency of cooling circuit depending on the charge of the previous and new alternative refrigerant.
- Identifiant de la fiche : 30022389
- Langues : Anglais
- Source : Compressors 2017: 9th International Conference on Compressors and Coolants.
- Date d'édition : 06/09/2017
- DOI : http://dx.doi.org/10.18462/iir.compr.2017.0209
Liens
Voir d'autres communications du même compte rendu (35)
Voir le compte rendu de la conférence
Indexation
-
A novel distributed scroll booster architecture...
- Auteurs : SAUNDERS M., RAJENDRAN R., BORN J., PATENAUDE A.
- Date : 05/2021
- Langues : Anglais
- Source : 2021 Purdue Conferences. 18th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Supermarket refrigeration system charge reducti...
- Auteurs : SHARMA V., FRICKE B., BANSAL P.
- Date : 02/08/2014
- Langues : Anglais
- Source : 11th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2014). Proceedings. Hangzhou, China, August 31-September 2, 2014.
- Formats : PDF
Voir la fiche
-
Practical experiences with ammonia refrigeratin...
- Auteurs : KOSI F. F.
- Date : 09/05/2013
- Langues : Anglais
- Source : 5th Conference on Ammonia Refrigeration Technology. Proceedings: Ohrid, North Macedonia, May 9-11, 2013.
- Formats : PDF
Voir la fiche
-
Energy performance of low-charge NH3 systems in...
- Auteurs : JENSEN S. S.
- Date : 08/2016
- Langues : Anglais
- Source : EcoLibrium - vol. 15 - n. 7
- Formats : PDF
Voir la fiche
-
Remplacement du R22 par des mélanges de frigori...
- Auteurs : REISS M.
- Date : 22/11/1995
- Langues : Allemand
- Source : DKV-Tagungsbericht 1995, Ulm.
Voir la fiche