Élaboration d'une nouvelle cartographie du givrage pour superviser le contrôle du dégivrage dans les systèmes de pompes à chaleur aérothermiques.

Developing a new frosting map to guide defrosting control for air-source heat pump units.

Auteurs : ZHU J. H., SUN Y. Y., WANG W., et al.

Type d'article : Article

Résumé

The development of a new frosting map for air-source heat pumps (ASHPs) based on a temperature-humidity chart is reported in this paper. Through a parametric analysis, two boundary lines (a condensing line and a frosting line) were obtained, dividing the map into three regions: a non-frosting region, a condensing region and a frosting region. Using the simulation results from a generalized numerical model of frost growth, the frosting region was further divided into three indicative zones representing different frosting levels: a severe frosting zone, a moderate frosting zone (I, II) and a mild frosting zone (I, II). Lab and field tests were conducted in order to verify the correctness of the zoning and to obtain indicative defrosting intervals for ASHPs operated at different zones. Based on the test results and using the developed map, reference defrosting intervals were suggested for different frosting zones, and they can be used in conjunction with a conventional defrosting control method to avoid potential mal-defrosting.

Détails

  • Titre original : Developing a new frosting map to guide defrosting control for air-source heat pump units.
  • Identifiant de la fiche : 30016701
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 90
  • Date d'édition : 05/11/2015
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2015.06.076

Liens


Voir d'autres articles du même numéro (21)
Voir la source