Encrassement des tubes à surface augmentée utilisant l'eau issue d'une tour de refroidissement. 1. Données sur l'encrassement à long terme.

Fouling in enhanced tubes using cooling tower water. 1. Long-term fouling data.

Auteurs : WEBB R. L., LI W.

Type d'article : Article

Résumé

The data were taken using 800 ppm calcium hardness water supplied to an operating chiller/cooling tower system. The fouling mechanism is a combination of precipitation fouling and particulate fouling. Fouling data were measured for seven different enhanced tube geometries over a 2500 h operating period. Little fouling occurred until 1300 h. After 1300 h. moderate fouling began to occur in the tubes having a large number of starts. These tubes also provide the highest water-side heat transfer coefficients. The salient finding of this first part of the work is that the potential for fouling increases as the number of starts and helix angle increases.

Détails

  • Titre original : Fouling in enhanced tubes using cooling tower water. 1. Long-term fouling data.
  • Identifiant de la fiche : 2001-1294
  • Langues : Anglais
  • Source : International Journal of Heat and Mass Transfer - vol. 43 - n. 19
  • Date d'édition : 10/2000