Document IIF
Essai, simulation et optimisation légère des frigorigènes alternatifs à faible GWP au R410A dans un système de pompe à chaleur.
Testing, simulation and soft-optimization of R410A low-GWP alternatives in heat pump system.
Auteurs : ALABDULKAREM A., ELDEEB R., HWANG Y., et al.
Type d'article : Article, Article de la RIF
Résumé
The environmental impact of high global warming potential (GWP) refrigerants pushed the HVAC&R industry to investigate alternative refrigerants. R410A is a common refrigerant for air conditioning and heat pumping applications, but has a GWP of 2088. Drop-in tests of three R410A low-GWP alternative refrigerants (R32, D2Y60 and L41a) in a 10.55?kW capacity split heat pump unit were performed. The results show that R32 and L41a are good replacement candidates for R410A. A finite volume heat exchanger model and component based vapor compression system simulation tools were validated against the experimental data. Most of the predicted COP and capacity results of R32 experiments lie within 5% of the measured values, which is in good agreement with the experiments. Further investigation was carried out by varying the size of the compressor and adding a suction line heat exchanger to the system to match the capacity to that of R410A.
Documents disponibles
Format PDF
Pages : 106-117
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Testing, simulation and soft-optimization of R410A low-GWP alternatives in heat pump system.
- Identifiant de la fiche : 30016324
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 60
- Date d'édition : 12/2015
Liens
Voir d'autres articles du même numéro (26)
Voir la source
Indexation
-
Thèmes :
Techniques des pompes à chaleur;
HFC;
Mélanges;
Efficacité energétique, économie d'énergie - Mots-clés : R410A; R32; Substitut; Simulation; Pompe à chaleur; Optimisation; GWP; Frigorigène
-
Steady state and transient validation of heat p...
- Auteurs : BHANOT V., BACELLAR D., LING J., et al.
- Date : 14/07/2014
- Langues : Anglais
- Source : 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Drop in life cycle climate performance of low G...
- Auteurs : LI G., ALABDULKAREM A., HWANG Y., et al.
- Date : 02/08/2014
- Langues : Anglais
- Source : 11th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2014). Proceedings. Hangzhou, China, August 31-September 2, 2014.
- Formats : PDF
Voir la fiche
-
Evaluation and soft-optimization for R410A low-...
- Auteurs : ALABDULKAREM A., ELDEEB R., HWANG Y., et al.
- Date : 14/07/2014
- Langues : Anglais
- Source : 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Nytt på köldmediefronten: alternativa köldmedie...
- Auteurs : MAKHNATCH P., KHODABANDEH R., PALM B.
- Date : 2012
- Langues : Suédois
- Source : KYLA+ Värmepumpar - n. 6
Voir la fiche
-
Evaluation of performance of heat pump system u...
- Auteurs : TAIRA S., HAIKAWA T.
- Date : 14/07/2014
- Langues : Anglais
- Source : 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche