Document IIF

Établissement d'une conception expérimentale dans le contexte d'une vaporisation d'eau se produisant sur une section transversale de plaque.

Establishment of an experimental design in the context of water vaporization occurring on a plate cross section.

Numéro : pap. n. 542

Auteurs : GIRAUD F., TOUBLANC C., RULLIERE R., et al.

Résumé

Compact evaporator like plate heat exchangers can play a significant role in reducing the investment cost of low cooling power sorption systems. If water is used as refrigerant, their design remain manly empirical. There is thus a need of better characterization of the influence of the driving parameters in order to optimize the evaporator design. An experimental design approach was chosen to understand the influence and the importance of each factor on evaporator performance. The test bench developed for this purpose allows to study flow regime inside the channel from a macroscopic point of view by means of a high speed camera. Three different boiling regimes were observed; however, significant cooling capacities (up to 500 W) were obtained when heat is transferred by evaporation induced by the spread of liquid by a bubble. Optimal liquid heights for interesting point were predicted from 1/5 to 1/3 of the plate.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Establishment of an experimental design in the context of water vaporization occurring on a plate cross section.
  • Identifiant de la fiche : 30016043
  • Langues : Anglais
  • Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
  • Date d'édition : 16/08/2015
  • DOI : http://dx.doi.org/10.18462/iir.icr.2015.0542

Liens


Voir d'autres communications du même compte rendu (657)
Voir le compte rendu de la conférence