ETABLISSEMENT ET VALIDATION D'UN MODELE DE REFROIDISSEUR D'EAU A COMPRESSEUR ALTERNATIF POUR LES PROGRAMMES D'ANALYSE HORAIRE DE L'ENERGIE.

DEVELOPMENT AND VALIDATION OF A RECIPROCATING CHILLER MODEL FOR HOURLY ENERGY ANALYSIS PROGRAMS.

Résumé

CE RAPPORT DECRIT L'ETABLISSEMENT D'UN MODELE DE REFROIDISSEUR A COMPRESSEUR ALTERNATIF A UTILISER DANS DES PROGRAMMES DE SIMULATION PAR ORDINATEUR POUR L'ANALYSE DE LA CONSOMMATION HORAIRE D'ENERGIE DES BATIMENTS. CE MODELE EST VALIDE PAR RAPPORT AUX PERFORMANCES MESUREES SUR UN REFROIDISSEUR A COMPRESSEUR ALTERNATIF AYANT UNE PUISSANCE FRIGORIFIQUE DE 70 KILOW FONCTIONNANT DANS UNE INSTALLATION EXPERIMENTALE POUR SIMULER UN SYSTEME CLASSIQUE DE CHAUFFAGE, VENTILATION ET CONDITIONNEMENT D'AIR A QUATRE ZONES. LA PERFORMANCE MESUREE DU REFROIDISSEUR ET LA PERFORMANCE DU MODELE CONCORDAIENT A MOINS DE 5,4 % PRES POUR TOUS LES POINTS DE FONCTIONNEMENT. CETTE CONCORDANCE SE SITUE DANS LES LIMITES DE LA PRECISION EXPERIMENTALE DES MESURES.

Détails

  • Titre original : DEVELOPMENT AND VALIDATION OF A RECIPROCATING CHILLER MODEL FOR HOURLY ENERGY ANALYSIS PROGRAMS.
  • Identifiant de la fiche : 1984-1988
  • Langues : Anglais
  • Date d'édition : 1983
  • Source : Source : ASHRAE Trans.
    vol. 89; n. 1A; 156-174; 11 fig.; 7 tabl.; 1 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.