Document IIF

Étude d’un système de pompe à chaleur à haute température à compression multiétagée avec du R-718 et d’autres frigorigènes à faible PRP.

Investigation on multi-stage compression high-temperature heat pump system based on R718 and other low GWP refrigerants.

Auteurs : SHI X., ZHANG C., LIU Y., WANG F.

Type d'article : Article de la RIF

Résumé

Under the dual-carbon strategy, electrifying industrial heating is a key trend. This study develops three types of thermodynamic cycle models for compression high-temperature heat pump (HTHP) systems. The effects of evaporation temperature on the compression characteristics of R718, R245fa, R1234ze(Z), and R1336mzz(Z) are investigated, along with an analysis of the available energy variation within the system. Results show that R718 exhibits superior thermodynamic properties compared to other refrigerants at high evaporation temperatures, with its coefficient of performance (COP) increasing from 4.70 to 5.34. However, the high pressure ratio and excessive superheat (up to 150 ◦C at 90 ◦C evaporation temperature) limits its practical application. When the lifting temperature is set at 40 ◦C, the three-stage compression (THC) system achieves an optimal performance value of 5.47, with a pressure ratio of 1.58 and exhaust superheat of 35.38 ◦C. The exergy efficiency of the threestage compression (TWC) and THC systems using R718 is 39.6 % and 56.1 % higher than that of the single-stage compression (SC) system at a waste heat source temperature of 95 ◦C, respectively. These findings emphasize
that multi-stage compression significantly enhances energy efficiency. Furthermore, this study provides valuable guidance for practical engineering applications.

Documents disponibles

Format PDF

Pages : 16 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Investigation on multi-stage compression high-temperature heat pump system based on R718 and other low GWP refrigerants.
  • Identifiant de la fiche : 30034285
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 176
  • Date d'édition : 08/2025
  • DOI : http://dx.doi.org/https://doi.org/10.1016/j.ijrefrig.2025.04.019

Liens


Voir d'autres articles du même numéro (30)
Voir la source

Indexation

  • Thèmes : N/A
  • Mots-clés : N/A