Étude de faisabilité et simulation numérique d'un système à pompe à chaleur géothermique, appliqué à un immeuble résidentiel.

Feasibility study and numerical simulation of a ground source heat pump plant, applied to a residential building.

Auteurs : DESIDERI U., SORBI N., ARCIONI L., et al.

Type d'article : Article

Résumé

To evaluate the efficiency of ground source heat pump (GSHP), an application is studied in a residential building divided in two independent apartments blocks. The numerical results are produced by using the software tool TRNSYS 16. The results include the trends of the thermo-climatic variables and a comparison between conventional and geothermal systems analyzing operational and capital costs. The GSHP studied in this paper produces a thermal power output of 29 kW in winter and a cooling power output of 26 kW during summer time. The numerical simulations have highlighted that with such a system, the GSHP has a winter coefficient of performance of 4.9, and a warm season coefficient of performance which reaches 2.3. The simulations show that the best plant configuration consists of a winter heating GSHP system and a summer freecooling bypass. The thermo-climatic variables inside the building provide good comfort conditions.

Détails

  • Titre original : Feasibility study and numerical simulation of a ground source heat pump plant, applied to a residential building.
  • Identifiant de la fiche : 30005339
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 31 - n. 16
  • Date d'édition : 11/2011
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2011.07.003

Liens


Voir d'autres articles du même numéro (19)
Voir la source