Document IIF

Etude de l'amélioration de l'efficacité d'un système de climatisation monobloc avec pompe et devant fonctionner toute l'année.

Study on efficiency improvement of year-round cooling packaged air conditioners with a refrigerant pump.

Résumé

In the paper, with the goal of enhancing the efficiency of year-round cooling packaged air conditioners, the authors add a refrigerant pump to be implemented in the compression cycle and only operate it during periods of low outdoor air temperature. Through laboratory testing and simulation, they established that the degree of superheat at the evaporator outlet should be controlled by the refrigerant pump frequency and the equipment room temperature should be regulated by the frequency of the condenser fan.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Study on efficiency improvement of year-round cooling packaged air conditioners with a refrigerant pump.
  • Identifiant de la fiche : 2004-0343
  • Langues : Anglais
  • Source : 21st IIR International Congress of Refrigeration: Serving the Needs of Mankind.
  • Date d'édition : 17/08/2003

Liens


Voir d'autres communications du même compte rendu (398)
Voir le compte rendu de la conférence