Étude du potentiel d’économie d’énergie d’un nouveau conditionneur d’air à deux températures et du mécanisme du cycle frigorifique théorique mélangé.

[In Chinese. / En chinois.]

Auteurs : ZHAO L., ZHAO X.

Type d'article : Article

Résumé

An innovative dual-temperature air conditioning system and the corresponding mixed theoretical refrigeration cycle were proposed. The new air-conditioner consists of an air handling unit and a metal radiation panel as its dual-temperature evaporators, a compressor, a condenser, two thermal expansion valves and an ejector. The state properties in the air handling process and the theoretical refrigeration cycle were analyzed and compared with those of the conventional air conditioner with fresh air. Results indicate that the coefficient of performance (COP) of the dual-temperature theoretical refrigeration cycle may be improved by 13.73 % to 7.43. But the COP of the dual-temperature refrigeration cycle will drop by somewhat as the amount of fresh air required and indoor moisture increases. However, it is still greater than the COP of the conventional air conditioner by 5.21 %.

Documents disponibles

Format PDF

Pages : 96-101

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 30020646
  • Langues : Chinois
  • Source : Journal of Refrigeration - vol. 35 - n. 160
  • Date d'édition : 12/2014

Liens


Voir d'autres articles du même numéro (11)
Voir la source