Étude expérimentale d’une nouvelle tour de refroidissement par évaporation en circuit fermé sans matelas dispersant, équipée de tubes de déformation tridimensionnelle verticaux
Experimental study of a novel non-packing closed evaporative cooling tower with vertical 3D deformation tubes.
Résumé
The closed evaporative cooling tower (CECT) is widely used in the field of industrial cooling. At present, most CECTs still mainly adopt the horizontal-tube falling-film cooling method. In this paper, a novel vertical CECT using 3D deformation tubes is developed. To investigate the vertical surface falling-film evaporative cooling effect of this novel cooling equipment, a traditional horizontal CECT was modified to produce a prototype of vertical non-packing CECT. The cooling performance of the novel vertical CECT has been investigated and compared to the previous traditional horizontal CECT by experimental method. The results show that the convective heat transfer coefficient of the water film outside the tube was increased by 5.87~12.95% and the overall cooling performance was increased by 7.31% on average. This indicates that the cooling load can be increased by changing the traditional horizontal-tube falling-film evaporative cooling method to the vertical falling-film evaporative cooling method. Moreover, the heat flux of the novel vertical CECT decreases by about 7% when the wet bulb temperature increases by 1 °C under the test range of wet bulb temperature, which indicates that the ambient wet bulb temperature has an obvious influence on the cooling load. The research results can provide reference for the optimization design of the CECT.
Documents disponibles
Format PDF
Pages : 13 p.
Disponible
Gratuit
Détails
- Titre original : Experimental study of a novel non-packing closed evaporative cooling tower with vertical 3D deformation tubes.
- Identifiant de la fiche : 30031231
- Langues : Anglais
- Sujet : Technologie
- Source : Energies - vol. 15 - n. 24
- Éditeurs : MDPI
- Date d'édition : 12/2022
- DOI : http://dx.doi.org/https://doi.org/10.3390/en15249336
Liens
Voir d'autres articles du même numéro (16)
Voir la source
-
Effect of heat rejection load and wet bulb on c...
- Auteurs : SCHWEDLER M.
- Date : 01/2014
- Langues : Anglais
- Source : ASHRAE Journal - vol. 56 - n. 1
Voir la fiche
-
Economic and Technical Analysis of a Hybrid Dry...
- Auteurs : TAIMOOR A. A., SAEED U., RATHER S-U., AL-SHAHRANI S., BAMUFLEH H. S., ALHUMADE H., SULAIMON A. A., ALALAYAH W. M., SHARIFF A. M.
- Date : 11/2022
- Langues : Anglais
- Source : Energies - vol. 15 - n. 21
- Formats : PDF
Voir la fiche
-
Performance investigation of plain circular and...
- Auteurs : HASAN A., SIRÉN K.
- Date : 04/2004
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 24 - n. 5-6
Voir la fiche
-
A study on an optimal approach temperature cont...
- Auteurs : LIU C. W., CHUAH Y. K.
- Date : 05/2011
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 34 - n. 3
- Formats : PDF
Voir la fiche
-
The performance of natural draught dry cooling ...
- Auteurs : WAKED R. al-, BEHNIA M.
- Date : 02/2004
- Langues : Anglais
- Source : Int. J. Energy Res. - vol. 28 - n. 2
Voir la fiche