Etude expérimentale de l'écoulement de R134a dans les tubes capillaires adiabatiques et diabatiques.

Experimental investigation of the flow of R134a through adiabatic and diabatic capillary tubes.

Résumé

This paper presents the experimental investigation of the flow of refrigerant R134a through adiabatic and diabatic capillary tube operating under similar conditions. The effect of various input parameters, such as capillary tube diameter, capillary tube length, and capillary tube inlet subcooling on the mass flow rate of R134a through a capillary tube under adiabatic and diabatic flow conditions, has been studied. The inlet pressure has been kept constant for both types of capillary tube. It has been observed that the suction-line superheat has an interfering effect on the mass flow rate through diabatic capillary tube. The acquired data from the present experimental setup have been analyzed, and separate empirical correlations to predict the mass flow rate through adiabatic and diabatic capillary tubes have been proposed. The mass flow rates predicted by the proposed correlations lie within the error band of plus or minus 10%.

Détails

  • Titre original : Experimental investigation of the flow of R134a through adiabatic and diabatic capillary tubes.
  • Identifiant de la fiche : 2009-2342
  • Langues : Anglais
  • Source : ASHRAE Transactions. Papers presented at the 2009 ASHRAE Winter Conference: Chicago, Illinois, January 2009. Volume 115, part 1.
  • Date d'édition : 25/01/2009

Liens


Voir d'autres communications du même compte rendu (20)
Voir le compte rendu de la conférence