Document IIF

Étude expérimentale de la performance du R454B comme frigorigène de remplacement immédiat dans une pompe à chaleur liquide-eau au R410A.

Experimental study of R454B drop-in performance in a R410A liquid-to-water heat pump.

Numéro : pap. n. 1535

Auteurs : ORTEGA I., SIERES J., CERDEIRA F., et al.

Résumé

R410A is a widely used refrigerant in residential heat pumps. The Global Warming Potential (GWP) of refrigerant R410A is 1924 so lower GWPalternatives are being studied in the last years as potential replacements of R410A. One potential alternative is refrigerant R454B with a GWP equal to 466.This paper presents an experimental study of the R454B drop-in performance in a R410A liquid-to-water heat pump. The main components of the heat pump are a scroll type compressor, two brazed plate heat exchangers (condenser and evaporator) and an electronic expansion valve. Experimental results for typical operating conditions of liquid-to-water heat pumps (EN 14511-2, 2013) are presented and discussed. From the experimental measurements, parameters such as the COP, heating power or compressor electric power consumption are obtained and compared between the two refrigerants. Results show that R454B might be an adequate drop-in refrigerant for R410A as it closely matches its performance.

Documents disponibles

Format PDF

Pages : 8

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental study of R454B drop-in performance in a R410A liquid-to-water heat pump.
  • Identifiant de la fiche : 30026121
  • Langues : Anglais
  • Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Date d'édition : 24/08/2019
  • DOI : http://dx.doi.org/10.18462/iir.icr.2019.1535

Liens


Voir d'autres communications du même compte rendu (632)
Voir le compte rendu de la conférence