Document IIF
Étude expérimentale des performances de fonctionnement des étages basse et haute température pour les pompes à chaleur aérothermiques en cascade.
Experimental study on operating performances of the low and high temperature stages for cascade air source heat pumps.
Résumé
Previous studies on cascade air source heat pumps (CASHPs) mainly focused on overall performances, while impacts of the low temperature stage (LTS) and high temperature stage (HTS) on overall performances were paid less attention to. Therefore, operating performances of a CASHP in LTS and HTS were investigated in this paper, to provide a solution for the optimization of the CASHP. A CASHP unit with a variable speed compressor in LTS and a constant speed compressor in HTS was adopted, and its operating performances were investigated under 26 cases. Results showed that the pressure ratio and COP in LTS and HTS were affected differently by the compressor speed. Specifically, as the speed of the compressor in LTS increased from 30 rps to 90 rps, PrL increased by 151 % ∼ 178 %, and PrH reduced by 38 % ∼ 54 %. Meanwhile, COP in LTS reduced by 21 % ∼ 52 %, but the COP in HTS rose by 54 % ∼ 96 %. Besides, it was found that adjustments of the compressor speed in LTS could improve heating performances of the CASHP. However, when the ambient air temperature and the supply water temperature were consistent, COP changes of the CASHP were limited, only by 0.3 % ∼ 9 %. Furthermore, empirical models of the COP in LTS and HTS were established to predict the COP of the CASHP on different operating conditions. Results of this study were helpful in promoting the configurations and operation control optimization of CASHPs.
Documents disponibles
Format PDF
Pages : 127-136
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Experimental study on operating performances of the low and high temperature stages for cascade air source heat pumps.
- Identifiant de la fiche : 30032795
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 167
- Date d'édition : 11/2024
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2024.07.017
Liens
Voir d'autres articles du même numéro (22)
Voir la source
Indexation
- Thèmes : Techniques des pompes à chaleur
- Mots-clés : Pompe à chaleur; Air; Système biétage; COP; Experimentation
-
Expérience sur un système de chauffage d'eau bi...
- Auteurs : WU W., WANG W., JIN S., et al.
- Date : 02/2009
- Langues : Chinois
- Source : Journal of Refrigeration - vol. 30 - n. 1
- Formats : PDF
Voir la fiche
-
Development and experimental investigation on t...
- Auteurs : TIAN C. Q., LIANG N., SHI W. X., et al.
- Date : 17/07/2006
- Langues : Anglais
- Source : 2006 Purdue Conferences. 18th International Compressor Engineering Conference at Purdue & 11th International Refrigeration and Air-Conditioning Conference at Purdue [CD-ROM].
- Formats : PDF
Voir la fiche
-
Performance evaluation of a 2-stage CO2 heat pu...
- Auteurs : KUWABARA O., KOBAYASHI M., MUKAIYAMA H., et al.
- Date : 21/08/2007
- Langues : Anglais
- Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
- Formats : PDF
Voir la fiche
-
Expérience sur la performance du givrage d'une ...
- Auteurs : JIN N., LI S., ZHANG K., et al.
- Date : 10/2010
- Langues : Chinois
- Source : Journal of Refrigeration - vol. 31 - n. 5
- Formats : PDF
Voir la fiche
-
HSPF calculation of an economizer double-staged...
- Auteurs : BARBOUCHI S., RITZ J. B., CLODIC D.
- Date : 09/10/2008
- Langues : Anglais
- Source : Scientific symposium: industrial cooling and thermodynamic systems. The Pôle Cristal meetings. [CD-ROM + 4 DVDs]. / Colloque scientifique : froid industriel et systèmes thermodynamiques. Les rendez-vous du Pôle Cristal. [CD-ROM + 4 DVD].
- Formats : PDF
Voir la fiche