Étude expérimentale sur la performance de déshumidification de systèmes à déshydratant liquide.

[In Chinese. / En chinois.]

Auteurs : ZOU T., ZHANG T., MA S., et al.

Type d'article : Article

Résumé

Through orthogonal experiment design, experimentally studies influences of mass fraction and temperature of inlet liquid, inlet liquid-air ratio, and humidity ratio and temperature of inlet air on the humidity ratio of outlet air. The results show that the first four factors affect significantly the dehumidifying capacity, and the effect of inlet air temperature is week; when the inlet liquid-air ratio value is smaller, the dehumidifying capacity increases along with the inlet liquid-air ratio; when the inlet liquid-air ratio is larger than 1.5, the dehumidifying capacity does almost not change along with the inlet liquid-air ratio; the sequencing of the five factors in the influence on unit dehumidifying capacity from large to small is the humidity ratio of inlet air, mass fraction of inlet liquid, temperature of inlet liquid, inlet liquid-air ratio and temperature of inlet air.

Documents disponibles

Format PDF

Pages : 76-79

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 30009606
  • Langues : Chinois
  • Source : HV & AC - vol. 43 - n. 273
  • Date d'édition : 01/2013

Liens


Voir d'autres articles du même numéro (9)