Résumé

The experiments on mass flow rate characteristics of R245fa refrigerant flowing through throttling devices including seven capillary tubes and the electronic expansion valve were carried out under the high-temperature working conditions. By combining regression analysis with flow correlations, the design basis that is applicable to R245fa throttling devices can be obtained. By comparing the experimental data with predicted data by Jung Correlation and Kim Correlation, it can be concluded that root mean square deviations of two correlations are 3.2 % and 3.3%, respectively. The root mean square deviation for electronic expansion valve is 4.5%. The conclusions offer highaccuracy design basis for throttling devices selection of high-temperature heat pump systems using R245fa as refrigerant.

Documents disponibles

Format PDF

Pages : 7

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental investigation on R245fa throttling devices under high temperature.
  • Identifiant de la fiche : 30024532
  • Langues : Anglais
  • Source : 2018 Purdue Conferences. 17th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Date d'édition : 09/07/2018

Liens


Voir d'autres communications du même compte rendu (252)
Voir le compte rendu de la conférence