Etude expérimentale sur un système de refroidissement à roue déshydratante biétagée.

Experimental study on a two-stage rotary desiccant cooling system.

Auteurs : GE T. S., LI Y., WANG R. Z., et al.

Type d'article : Article, Article de la RIF

Résumé

The objectives of this study were to evaluate the performance of a novel two-stage rotary desiccant cooling (TSRDC) system and to obtain useful data and experiences for practical application. Newly developed compound desiccant (silica gel-haloids) was adopted in the system. An experimental set-up was built and used to test the system performance under three typical environmental conditions. System performances were evaluated in terms of moisture removal D and thermal coefficient of performance COP(th). It has found that the required regeneration temperature of TSRDC system is low and COP(th) of the system is high. Regeneration temperatures from 65 to 80, 65 to 75 and 80 to 90°C were recommended for each environmental condition. In addition, the effects of some important operating parameters, such as inlet temperature and humidity ratio of process and regeneration air, on system performance were also investigated in this study.

Documents disponibles

Format PDF

Pages : 498-508

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental study on a two-stage rotary desiccant cooling system.
  • Identifiant de la fiche : 2009-0746
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 3
  • Date d'édition : 05/2009

Liens


Voir d'autres articles du même numéro (18)