Étude par simulation d'un système de froid / pompe à chaleur à machine unique et à double chambre en compression parallèle.

[In Chinese. / En chinois.]

Auteurs : XU S., MA G., LIU Q., et al.

Type d'article : Article

Résumé

In order to improve the working performance of vapor compression refrigeration/heat pump system, a new system named single machine two-chamber in-parallel compression refrigeration/heat pump system was provided. An analysis model was set according to the theory of thermodynamics. The variation of cooling and heating performance with side-stage suction pressure and the most favorable volume ratio of side-stage to main-stage have been calculated. The results show that, compared with conventional single-stage compression system, cooling and heating capacity can increase 29.6% and 29.2%; cooling EER and heating COP can increase 8.0% and 2.8%; the discharge temperature decrease 3~4°C. The most favorable volume ratio of side-stage to main-stage is 0.08~0.12.

Documents disponibles

Format PDF

Pages : 1-4, 34