Etude sur les caractéristiques en charge partielle des systèmes à absorption à double effet.

[In Japanese. / En japonais.]

Auteurs : KAWAKAMI R., FUKUCHI T., KAITA Y.

Type d'article : Article

Résumé

Simulation analysis was carried out in order to study the partial load characteristics of three different types of double effect LiBr-water absorption cycle, namely series flow, parallel flow and reverse flow. A computer programme was developed for this study in order to simulate the behaviour of the absorption cycles equipped with rate control of absorbent, cooling water and chilling water partial load. The effects of the flow rate control on the COP, the maximum temperature and maximum pressure were studied. The results show that not only flow rate control of absorbent is essential for high COP on the partial load, but also flow rate control of cooling water and chilling water is recommendable to save the power of pumping.

Détails

  • Titre original : [In Japanese. / En japonais.]
  • Identifiant de la fiche : 2006-0742
  • Langues : Japonais
  • Source : Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 21 - n. 3
  • Date d'édition : 2004

Liens


Voir d'autres articles du même numéro (5)
Voir la source