Evaluation comparative de deux schémas de récupération de chaleur appliquées à un refroidisseur à adsorption à deux lits.

A comparative evaluation of two different heat-recovery schemes as applied to a two-bed adsorption chiller.

Auteurs : WANG X., CHUA H. T.

Type d'article : Article

Résumé

This study investigates the efficiency of two distinct heat-recovery schemes as applied to the two-bed silica gel-water adsorption chiller. Performance predictions stemming from an experimentally verified distributed-parameter model compare favorably with the experimental results at various operating conditions. This study highlights the pivotal role played by heat-recovery schemes to ameliorate the chiller performance and substantially improve the COP. The two different schemes essentially offer the same cooling capacity and similar COP boosting capability. In the studied working conditions of a two-bed adsorption chiller, the difference in COP by using the two schemes is less than 5%. [Reprinted with permission from Elsevier. Copyright, 2006].

Détails

  • Titre original : A comparative evaluation of two different heat-recovery schemes as applied to a two-bed adsorption chiller.
  • Identifiant de la fiche : 2007-1106
  • Langues : Anglais
  • Source : International Journal of Heat and Mass Transfer - vol. 50 - n. 3-4
  • Date d'édition : 02/2007

Liens


Voir d'autres articles du même numéro (6)
Voir la source