Document IIF

Évaluation de la performance d'un détecteur virtuel de la charge en frigorigène.

Performance evaluation of a virtual refrigerant charge sensor.

Auteurs : KIM W., BRAUN J. E.

Type d'article : Article, Article de la RIF

Résumé

The primary goal was to evaluate and enhance a virtual refrigerant charge (VRC) sensor developed by Li and Braun (2006, 2009). Based on the evaluation, the VRC sensor was found to work well in estimating refrigerant charge for systems that do not utilize accumulators when using the default parameters. For systems with accumulators, however, the parameters needed to be improved for better accuracy. To overcome those limitations, a simulation method for estimating parameters was developed that depends on test data at rated conditions and system information. The simulation parameters decreased the errors between the actual and predicted charge. Even better performance was achieved for the VRC sensor when the parameters were tuned by minimizing charge prediction errors using test data and linear regression. The overall RMS error for the VRC sensors using tuned parameters was 3.8% over a wide range of operating conditions for different types of systems.

Documents disponibles

Format PDF

Pages : 1130-1141

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance evaluation of a virtual refrigerant charge sensor.
  • Identifiant de la fiche : 30008043
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 3
  • Date d'édition : 05/2013

Liens


Voir d'autres articles du même numéro (51)
Voir la source