Document IIF

Evaluation de la performance d'un système de refroidissement par évaporation et déshydratation.

Performance evaluation of a desiccant-evaporative cooling system.

Auteurs : SHEER T. J., THOM M. G.

Résumé

The system incorporated a rotary desiccant wheel impregnated with lithium chloride for humidity control and two-stage evaporative cooling, with a rotary sensible heat regenerator and high-efficiency spray chambers in the supply and return air ducts. A typical value of cooling capacity was 3 kilowatt, with a coefficient of performance of approximately 0,5. Several factors can seriously affect the performance of such a system (air leakage at the rotary exchangers, water carry-over from the return air spray chamber into the sensible heat regenerator, and desiccant degradation). Various methods of improving the energy efficiency and practicability of a desiccant-evaporative cooling system are suggested.

Documents disponibles

Format PDF

Pages : 1998-4

Document à numériser, disponible sous dix jours

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance evaluation of a desiccant-evaporative cooling system.
  • Identifiant de la fiche : 1999-2907
  • Langues : Anglais
  • Source : Natural Refrigerants, Energy Efficiency, Cost and Safety. Natural Working Fluids '98. IIR-Gustav Lorentzen Conference.
  • Date d'édition : 02/06/1998
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (65)
Voir le compte rendu de la conférence