Evaluation expérimentale de la performance thermique d'un système horizontal de pompes à chaleur sol-air.

Experimental thermal performance evaluation of a horizontal ground-source heat pump system.

Auteurs : INALLI M., ESEN H.

Type d'article : Article

Résumé

The goal of this study was to validate the effects of parameters such as the buried depth of an earth-coupled heat exchanger, the mass flow rate of the water-antifreeze solution and sewer water on the performance of a horizontal ground-source heat pump (GSHP) system used for space heating experimentally. The experimental results were obtained from November to April during the heating season of 2002-2003. The average performance coefficients of the system for a horizontal ground heat exchanger in the different trenches, at 1 and 2 m depths, were found to be 2.66 and 2.81, respectively. Results obtained from experimental measurement demonstrated that horizontal GSHP systems can be used for climatic conditions in Elazig, Turkey.

Détails

  • Titre original : Experimental thermal performance evaluation of a horizontal ground-source heat pump system.
  • Identifiant de la fiche : 2005-0970
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 24 - n. 14-15
  • Date d'édition : 10/2004