Document IIF
Évaluation semi-empirique du HCFO-1224yd(Z) en remplacement du HFC-245fa dans les pompes à chaleur à haute température.
Semi-empirical evaluation of HCFO-1224yd(z) as a replacement for HFC-245fa in high temperature heat pumps.
Numéro : 1117
Auteurs : MATEU-ROYO C., MOTA BABILONI A., MOLÉS F., AMAT-ALBUIXECH M., NAVARRO-ESBRÍ J.
Résumé
This paper investigates a promising low-GWP refrigerant HCFO-1224yd(Z) as an alternative replacement for HFC-245fa in high temperature heat pumps. A comprehensive thermophysical properties analysis was realised along with thermodynamic modelling of a single stage cycle with Internal Heat Exchanger (IHX) and semi-empirical drop-in test replacement. The heat source temperature was fixed in 80 ºC, whereas the heat sink temperature was varied from 110 to 140 ºC to cover a wide range of industrial applications. The theoretical and semi-empirical results illustrate that the heating capacity of HCFO-1224yd(Z) becomes around 8.9% lower than HFC-245fa. However, the higher suction density of HCFO-1224yd(Z) compared to the reference fluid can compensate this phenomenon, reducing the compressor power consumption. Hence, HCFO-1224yd(Z) presents a COP increase up to 4.5% compared to the reference fluid. At heat sink temperature of 140 ºC, HCFO-1224yd(Z) shows a COP of 2.33, whereas HFC-245fa has a value of 2.23. Therefore, HCFO-1224yd(Z) can be used as an alternative to HFC-245fa in high temperature heat pumps due to its proper thermophysical and environmental properties.
Documents disponibles
Format PDF
Pages : 8
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Semi-empirical evaluation of HCFO-1224yd(z) as a replacement for HFC-245fa in high temperature heat pumps.
- Identifiant de la fiche : 30027645
- Langues : Anglais
- Sujet : Alternatives aux HFC
- Source : IIR Rankine Conference 2020.
- Date d'édition : 31/07/2020
- DOI : http://dx.doi.org/10.18462/iir.rankine.2020.1117
Liens
Voir d'autres communications du même compte rendu (75)
Voir le compte rendu de la conférence
Indexation
-
Thermodynamic analysis of low GWP HFO and HCFO ...
- Auteurs : DIEWALD K., ARPAGAUS C., HEBENSTREIT B.
- Date : 31/07/2020
- Langues : Anglais
- Source : IIR Rankine Conference 2020.
- Formats : PDF
Voir la fiche
-
Experimental comparison of HCFO and HFO R1224yd...
- Auteurs : ARPAGAUS C., BERTSCH S. S.
- Date : 05/2021
- Langues : Anglais
- Source : 2021 Purdue Conferences. 18th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Theoretical study of low GWP refrigerants in hi...
- Auteurs : ZHANG F., MENG Z., DONG S., LIU S., DING C., HUO Z., WANG M.
- Date : 05/04/2023
- Langues : Anglais
- Source : 3rd IIR conference on HFO Refrigerants and low GWP Blends. Shanghai, China.
- Formats : PDF
Voir la fiche
-
Experimental comparison of HCFO R1233zd(E) and ...
- Auteurs : ARPAGAUS C., BERTSCH S. S.
- Date : 31/07/2020
- Langues : Anglais
- Source : IIR Rankine Conference 2020.
- Formats : PDF
Voir la fiche
-
High temperature heat pumps – Theoretical study...
- Auteurs : ARPAGAUS C., PRINZING M., KUSTER R., et al.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF