Document IIF
Évaporation par aspersion du mélange frigorigène R1234ze (E)/huile POE–68 sur des faisceaux de tubes améliorés.
Spray evaporation of R1234ze(E)/POE-68 refrigerant-oil mixture on enhanced tube bundles.
Auteurs : EBANESAR J. R., ROTHE J., CREMASCHI L.
Type d'article : Article de la RIF
Résumé
Lubricating oil is used in compressors of vapor compression-based refrigeration systems. The oil that escapes from the compressors inevitably circulates in the heat exchangers, affecting their thermal performances. This paper presents a comprehensive study on the impact of lubricating oil on the heat transfer performance of spray evaporator tube bundles used in air conditioning and refrigeration systems. The research includes valuable data on the heat transfer coefficient of tube bundles when subjected to refrigerant and lubricant mixtures of R134a (HFC) and R1234ze(E) (HFO) with synthetic polyolester (POE) lubricant. The investigation delves into the influence of three crucial factors: heat flux, oil circulation ratio (OCR), and saturation temperature. The saturation temperature was examined across a range of −6.7 to 10 °C (20–50 °F), while the heat flux was varied from 6 kW/m2 to 17 kW/m2. OCR was controlled at 1.2 %. The effects of oil on spray evaporation of R1234ze(E)/POE mixture on enhanced tube bundle was studied by varying tube surface structure and bundle layout, that is, square and triangular configurations.
The bundle heat transfer coefficient decreased by at least 10 % when lubricant was present in the mixture but, in some cases, varied by 50 % or more compared to the performances with refrigerant only (i.e., no lubricant). The data suggested that the oil penalized the heat transfer coefficient of the bottom tube rows of the bundle, which in many conditions, starved and experienced a partial-dry out state. Externally enhanced boiling-type tubes were more sensitive to the presence of oil than externally enhanced condenser-type tubes.
Documents disponibles
Format PDF
Pages : 163-175
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Spray evaporation of R1234ze(E)/POE-68 refrigerant-oil mixture on enhanced tube bundles.
- Identifiant de la fiche : 30032219
- Langues : Anglais
- Sujet : Technologie
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 159
- Date d'édition : 03/2024
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2023.12.017
Liens
Voir d'autres articles du même numéro (32)
Voir la source
-
Effect of lubricating oil on the refrigerant he...
- Auteurs : EBANESAR J. R., CREMASCHI L.
- Date : 2022
- Langues : Anglais
- Source : 2022 Purdue Conferences. 19th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Impact of oil presence on the evaporator enthal...
- Auteurs : SUN Y., WEI Q., WANG J., WANG X., HE M.
- Date : 09/2021
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 129
- Formats : PDF
Voir la fiche
-
Falling film evaporation experiment and data pr...
- Auteurs : OUYANG X. P., SUN K.
- Date : 02/2022
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 134
- Formats : PDF
Voir la fiche
-
An experimental investigation and correlation o...
- Auteurs : SUN Y., WANG J., WANG X., HE M., HU Y.
- Date : 01/2021
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 121
- Formats : PDF
Voir la fiche
-
Falling film evaporation and pool boiling of HF...
- Auteurs : UBARA T., SAWATARI K., SUGIMOTO K., ASANO H.
- Date : 06/2021
- Langues : Anglais
- Source : 2nd IIR Conference on HFO Refrigerants and Low GWP Blends
- Formats : PDF
Voir la fiche