Document IIF
Experimental assessment of the use of R515B as R1234ze(E) alternative in a small water-to-water heat pump.
Experimental assessment of the use of R515B as R1234ze(E) alternative in a small water-to-water heat pump.
Numéro : 0287
Auteurs : COLOMBO L. P. M., FRIGERIO D., LUCCHINI A., MOLINAROLI L.
Résumé
This paper presents the results of an experimental campaign carried out to assess the performance of a water-to-water heat pump working with R515B in a drop-in application. The heat pump is tested in a broad range of mass flow rates and temperatures of the secondary fluids at the heat exchangers outlets and the results are compared with those of R1234ze(E) since this refrigerant is the main component of the R515B mixture. In the range of the tested operating conditions, the use of R515B leads to capacity and COP variations that are within the ranges -4.70% to -0.92% and -1.86% to 3.74% respectively. From the compressor operation perspective, the use of R515B leads to slightly lower refrigerant temperature at the compressor discharge, with differences in the range -3.08 °C to -0.63 °C, whereas the volumetric efficiency is substantially the same.
Documents disponibles
Format PDF
Pages : 10
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Experimental assessment of the use of R515B as R1234ze(E) alternative in a small water-to-water heat pump.
- Identifiant de la fiche : 30031389
- Langues : Anglais
- Sujet : Technologie, Alternatives aux HFC
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Date d'édition : 21/08/2023
- DOI : http://dx.doi.org/10.18462/iir.icr.2023.0287
Liens
Voir d'autres communications du même compte rendu (491)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
HFO et HCFO;
Techniques des pompes à chaleur - Mots-clés : Experimentation; R515B; R1234ze(E); Eau-eau; Pompe à chaleur; Remplacement immediat; COP; Essai
-
Comparative analysis of HFO-1234ze(E) and R-515...
- Auteurs : MATEU-ROYO C., MOTA BABILONI A., NAVARRO-ESBRÍ J., BARRAGÁN-CERVERA A.
- Date : 04/2021
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 124
- Formats : PDF
Voir la fiche
-
Experimental analysis of the use of R1234yf and...
- Auteurs : COLOMBO L. P. M., LUCCHINI A., MOLINAROLI L.
- Date : 07/2020
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 115
- Formats : PDF
Voir la fiche
-
Evaluación experimental del R452b como sustitut...
- Auteurs : ORTEGA I., SIERES J., CERDEIRA F., ALVAREZ E., DOPAZO J. A.
- Date : 11/11/2020
- Langues : Espagnol
- Source : X Congreso Ibérico y VIII Congreso Iberoamericano de Ciencias y Técnicas del Frío, CYTEF 2020.
- Formats : PDF
Voir la fiche
-
Evaluation of high-temperature heat pump cycle ...
- Auteurs : FUKUDA S., KONDOU C., TAKATA N., et al.
- Date : 17/06/2013
- Langues : Anglais
- Source : 4th IIR Conference on Thermophysical Properties and Transfer Processes of Refrigerants
- Formats : PDF
Voir la fiche
-
Evaluación del ciclo de rendimiento de la bomba...
- Auteurs : FUKUDA S., KONDOU C., TAKATA N., et al.
- Date : 01/2015
- Langues : Espagnol
- Source : Frío Calor Aire acondicionado - vol. 43 - n. 476
- Formats : PDF
Voir la fiche