Driven by the Kigali Amendment, this study experimentally investigates condensation heat transfer and frictional characteristics of R134a, R1234yf, and R290 in water-cooled brazed plate heat exchangers with I-flow, X-flow, and three-pass configurations. Tests covered refrigerant-side Reynolds numbers of 200–3000 under typical air-conditioning and heat-pump conditions. Heat transfer was evaluated using Nu/Boⁿ, while flow resistance was characterized by the two-phase friction factor. Nu/Boⁿ increased with Re, whereas the friction factor decreased rapidly before stabilizing in the turbulent region. R290 consistently delivered the best condensation heat transfer performance. The three-pass design performed best at low-to-medium Re, while X-flow provided the strongest enhancement at high Re. I-flow produced the lowest pressure drop. Overall, R290 with the three-pass exchanger offered the best thermal-hydraulic performance under conventional conditions, whereas R290 with X-flow was preferable for high mass fluxes and large heat loads, providing practical guidance for low-GWP compact condensers in practical applications.
Documents disponibles
Format PDF
Pages : 12 p.
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Experimental Investigation on Bulk Condensation Characteristics of Low-GWP Refrigerants in Water-Cooled Plate Heat Exchangers with Three Flow Configurations.
- Identifiant de la fiche : 30035465
- Langues : Anglais
- Sujet : Technologie
- Source : 17th IIR-Gustav Lorentzen Conference on Natural Refrigerants. Proceedings. Hamilton, New Zealand, August 23-26 2026.
- Date d'édition : 08/2026
- DOI : http://dx.doi.org/10.18462/iir.gl2026.0116