Recommandé par l'IIF / Document IIF
Experimental results of a high-temperature heat pump prototype with R1336mzz(Z) for various production temperatures.
Experimental results of a high-temperature heat pump prototype with R1336mzz(Z) for various production temperatures.
Numéro : 0077
Auteurs : MOTA BABILONI A., BARRAGÁN-CERVERA A., UDROIU C-M., GIMÉNEZ-PRADES P., NAVARRO-ESBRÍ J.
Résumé
Vapour compression heat pumps are the most promising technologies for decarbonisation in high-temperature processes. This paper presents experimental data of a high-temperature heat pump prototype designed for R-245fa when operating with R1336mzz(Z). Forty-five steady-state experiments were performed in a scroll compressor prototype with a liquid-to-suction heat exchanger at production temperatures between 102 °C and 158 °C (temperature difference of the secondary fluid between 8.5 K and 22 K) and waste heat temperatures between 80 °C and 118 °C (temperature difference of the secondary fluid between 12.6 K and 47.5 K). The heating capacity varied between 9.9 kW and 13.4 kW, and the coefficient of performance was between 2.0 and 4.8. Compared to previous experimental results using R-245fa, R-1336mzz(Z) results in higher COP under the same operating conditions. A medium-to-low carbon emission factor would make this solution more environmentally friendly than a natural gas boiler for small-scale heating production.
Documents disponibles
Format PDF
Pages : 9
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Experimental results of a high-temperature heat pump prototype with R1336mzz(Z) for various production temperatures.
- Identifiant de la fiche : 30031370
- Langues : Anglais
- Sujet : Technologie
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Date d'édition : 21/08/2023
- DOI : http://dx.doi.org/10.18462/iir.icr.2023.0077
Liens
Voir d'autres communications du même compte rendu (491)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Techniques des pompes à chaleur;
HFO et HCFO;
HFC - Mots-clés : Haute température; Pompe à chaleur; R1336mzz(Z); Experimentation; Prototype; Chaleur perdue; COP; Faible GWP; R245fa
-
Experimental comparison of HCFO and HFO R1224yd...
- Auteurs : ARPAGAUS C., BERTSCH S. S.
- Date : 05/2021
- Langues : Anglais
- Source : 2021 Purdue Conferences. 18th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Miniature oil-less reciprocating compressor for...
- Auteurs : MURPHY D. L., KATANCIK M. S.
- Date : 05/2021
- Langues : Anglais
- Source : 2021 Purdue Conferences. 25th International Compressor Engineering Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Thermodynamic analysis of low GWP HFO and HCFO ...
- Auteurs : DIEWALD K., ARPAGAUS C., HEBENSTREIT B.
- Date : 31/07/2020
- Langues : Anglais
- Source : IIR Rankine Conference 2020.
- Formats : PDF
Voir la fiche
-
Theoretical performance evaluation of ejector a...
- Auteurs : MATEU-ROYO C., NAVARRO-ESBRÍ J., MOTA BABILONI A., BARRAGÁN-CERVERA A.
- Date : 11/2020
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 119
- Formats : PDF
Voir la fiche
-
Theoretical study of low GWP refrigerants in hi...
- Auteurs : ZHANG F., MENG Z., DONG S., LIU S., DING C., HUO Z., WANG M.
- Date : 05/04/2023
- Langues : Anglais
- Source : 3rd IIR conference on HFO Refrigerants and low GWP Blends. Shanghai, China.
- Formats : PDF
Voir la fiche