Recommandé par l'IIF / Document IIF
Gestion thermique à haut flux à l’échelle du mégawatt en utilisant un cycle frigorifique en cascade à double effet à absorption/compression de vapeur.
High-flux thermal management at megawatt scale using a double-effect absorption/vapor-compression cascade refrigeration cycle.
Auteurs : NAGAVARAPU A. K., GARIMELLA S.
Type d'article : Article de la RIF
Résumé
A robust, high-performance, cascaded double-effect absorption/vapor-compression cycle with a high temperature lift was conceptualized and analyzed for a naval ship application. A double-effect LiBr–H2O absorption cycle driven by high-temperature (>275°C) exhaust heat was coupled to a subcritical CO2 vapor-compression cycle to provide low temperature refrigerant (-40°C) for high-heat flux electronics applications and medium temperature refrigerant (5°C) for space conditioning and other low-heat flux applications. The double-effect absorption/vapor-compression cycle outperformed the corresponding single-effect cycle, providing 74.4% higher cooling capacity for the same waste heat input; however, it required more heat exchange area. The improved performance of the double-effect configuration was much higher at lower heat rejection temperatures. A parametric study on the exhaust and heat rejection temperatures showed that the cycle exhibited high COPs over a wide range of operating conditions, indicating the robustness of the cycle.
Documents disponibles
Format PDF
Pages : 257-267
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : High-flux thermal management at megawatt scale using a double-effect absorption/vapor-compression cascade refrigeration cycle.
- Identifiant de la fiche : 30027799
- Langues : Anglais
- Sujet : Technologie
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 119
- Date d'édition : 11/2020
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2020.08.005
Liens
Voir d'autres articles du même numéro (41)
Voir la source
-
Waste heat driven absorption/vapor-compression ...
- Auteurs : GARIMELLA S., BROWN A. M., NAGAVARAPU A. K.
- Date : 12/2011
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 34 - n. 8
- Formats : PDF
Voir la fiche
-
Waste heat driven absorption/vapour compression...
- Auteurs : GARIMELLA S., BROWN A. M., NAGAVARAPU A. K.
- Date : 06/04/2011
- Langues : Anglais
- Source : Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Formats : PDF
Voir la fiche
-
Simulation d'un système frigorifique à absorpti...
- Auteurs : HE J., YANG J.
- Date : 2004
- Langues : Chinois
- Source : Journal of Refrigeration - n. 3
- Formats : PDF
Voir la fiche
-
CONCEPTUAL THERMODYNAMIC DESIGN OF A DUAL MODE ...
- Auteurs : KAUSHIK S. C., KUMAR R.
- Date : 1989
- Langues : Anglais
- Source : Heat Recov. Syst. CHP - vol. 9 - n. 4
Voir la fiche
-
THERMODYNAMIC FEASIBILITY OF DOUBLE EFFECT GENE...
- Auteurs : KAUSHIK S. C., CHANDRA S., GADHI S. M. B.
- Date : 1985
- Langues : Anglais
- Source : J. Heat Recov. Syst. - vol. 5 - n. 1
Voir la fiche