GROSVENOR PLACE : ETUDE DE LA CONCEPTION DE L'ENERGIE INTEGREE.

GROSVENOR PLACE: A STUDY IN INTEGRATED ENERGY DESIGN.

Auteurs : THOMAS D. S.

Type d'article : Article

Résumé

LA REALISATION DE BUREAUX PROPOSEE POUR SYDNEY A ETE CONCUE POUR AVOIR UN BON RENDEMENT ENERGETIQUE. L'ORIENTATION DE LA TOUR DE 44 ETAGES EST CHOISIE POUR REDUIRE AU MINIMUM LES ENTREES DE CHALEUR SOLAIRE TANDIS QUE LES DOUBLES-FENETRES AVEC VITRES DE PROTECTION CONTRE LE SOLEIL AUGMENTENT AU MAXIMUM LA LUMIERE NATURELLE ET LA VISIBILITE. LES SYSTEMES DE PROTECTION SOLAIRE PRODUIRONT UN COEFFICIENT EFFECTIF DE 0,2, PERMETTANT D'UTILISER UN SYSTEME DE CONDITIONNEMENT D'AIR A DEBIT D'AIR VARIABLE. L'INSTALLATION UTILISE AU MAXIMUM L'ECHANGE D'ENERGIE A L'INTERIEUR DU SYSTEME, EN UTILISANT LA CHALEUR REJETEE PAR LE REFROIDISSEMENT, EN UTILISANT AU MAXIMUM L'AIR EXTERIEUR ET EN RECUPERANT LA CHALEUR DE L'AIR REJETE EN HIVER. DES PANNEAUX SOLAIRES PRODUISENT L'EAU CHAUDESANITAIRE. L'ECLAIRAGE EST CONCU POUR NE PAS DEPASSER 11 W/M2 DANS CERTAINES ZONES. ON DONNE UNE DESCRIPTION COMPLETE DES METHODES UTILISEES. ELLES PORTENT SUR LA AU CHAUDE ET LE BILAN THERMIQUE DU SYSTEME. D.W.H.

Détails

  • Titre original : GROSVENOR PLACE: A STUDY IN INTEGRATED ENERGY DESIGN.
  • Identifiant de la fiche : 1986-0776
  • Langues : Anglais
  • Source : Aust. Refrig. Air Cond. Heat. - vol. 39 - n. 1
  • Date d'édition : 01/1985
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (3)
Voir la source