Document IIF

HCFC22, HFC134a, HFC125 et HFC32 : coefficients de transfert de chaleur lors de l'ébullition nucléée sur différents tubes à surface augmentée.

Nucleate boiling heat transfer coefficients of HCFC22, HFC134a, HFC125, and HFC32 on various enhanced tubes.

Auteurs : JUNG D., AN K., PARK J.

Type d'article : Article, Article de la RIF

Résumé

In this study, nucleate boiling heat transfer coefficients (HTCs) of HCFC22, HFC134a, HFC125, HFC32 were measured on a low fin, Turbo-B, and Thermoexcel-E tubes. All data were taken at the liquid pool temperature of 7 °C on horizontal tubes of 152 mm length and 18.6-18.8 mm outside diameter at heat fluxes in decreasing order of heat flux. For a plain and low fin tubes, refrigerants with higher vapour pressures showed higher nucleate boiling HTCs consistently. This was due to the fact that the wall superheat required to activate given size cavities became smaller as pressure increased. For Turbo-B and Thermoexcel-E tubes, HFC125 showed a peculiar behavior exhibiting much reduced HTCs due to its high reduced pressure. The heat transfer enhancement ratios of the low fin, Turbo-B, and Thermoexcel-E tubes were 1.09-1.68, 1.77-5.41, 1.64-8.77 respectively in the range of heat fluxes tested.

Documents disponibles

Format PDF

Pages : 202-206

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Nucleate boiling heat transfer coefficients of HCFC22, HFC134a, HFC125, and HFC32 on various enhanced tubes.
  • Identifiant de la fiche : 2004-1067
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 27 - n. 2
  • Date d'édition : 03/2004