Impact de la géométrie des canalisations sur les caractéristiques des frigorigènes lors du transfert de chaleur par écoulement biphasique dans les échangeurs de chaleur à microcanalisation.

Impact of channel geometry on two-phase flow heat transfer characteristics of refrigerants in microchannel heat exchangers.

Auteurs : RAVIGURURAJAN T. S.

Type d'article : Article

Résumé

The results indicate that the heat transfer coefficient and pressure drop are functions of the flow quality, the mass flux and of course, the heat flux and the related surface superheat. The heat transfer coefficient decreases from a value of 12,000 to 9000 watts/(m2.K) at 80 deg C, when the wall superheat is increased from 10 to 80 deg C. The coefficient decreases by 30 percent when the exit vapour quality is increased from 0.01 to 0.65.

Détails

  • Titre original : Impact of channel geometry on two-phase flow heat transfer characteristics of refrigerants in microchannel heat exchangers.
  • Identifiant de la fiche : 1999-1489
  • Langues : Anglais
  • Source : J. Heat Transf. - vol. 120 - n. 2
  • Date d'édition : 05/1998
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.