INCONFORT THERMIQUE DU AUX COURANTS D'AIR ET A LA DIFFERENCE VERTICALE DE TEMPERATURE DANS DES PIECES AVEC UN SYSTEME DE VENTILATION PAR DEPLACEMENT.

LOCAL THERMAL DISCOMFORT DUE TO DRAFT AND VERTICAL TEMPERATURE DIFFERENCE IN ROOMS WITH DISPLACEMENT VENTILATION.

Résumé

DANS LE RAPPORT, ON EVALUE LES CONDITIONS DE CONFORT THERMIQUE DANS 18 ESPACES, VENTILES PAR UN SYSTEME A DEPLACEMENT D'AIR RECEMMENT DEVELOPPE EN SCANDINAVIE. ON EVALUE LE RISQUE D'INCONFORT THERMIQUE DU AUX COURANTS D'AIR ET A UNE DIFFERENCE VERTICALE DE TEMPERATURE PAR DES MESURES APPROFONDIES DE LA VITESSE MOYENNE DE L'AIR, DE L'INTENSITE DE LA TURBULENCE ET DE LA TEMPERATURE DE L'AIR. LES HAUTEURS DE MESURE POUR LA TEMPERATURE DE L'AIR ET LE MOUVEMENT DE L'AIR, RECOMMANDEES DANS LES NORMES (0,1 ; 0,6 ; 1,1 ET 1,7 M) SE SONT AVEREES INSUFFISANTES POUR EVALUER LE RISQUE DE COURANT D'AIR DANS LA ZONE OCCUPEE. ON A OBSERVE QUE LA VITESSE MOYENNE, L'INTENSITE DE LA TURBULENCE, LA TEMPERATURE DE L'AIR, LE POURCENTAGE PREVU DE PERSONNES INSATISFAITES A CAUSE DES COURANTS D'AIR ET DE LA DIFFERENCE VERTICALE DE TEMPERATURE, DEPENDAIENT DE LA DIFFERENCE DE TEMPERATURE ENTRE L'AIR EXTRAIT ET L'AIR SOUFFLE ET DU TAUX D'ECOULEMENT DE L'AIR.

Détails

  • Titre original : LOCAL THERMAL DISCOMFORT DUE TO DRAFT AND VERTICAL TEMPERATURE DIFFERENCE IN ROOMS WITH DISPLACEMENT VENTILATION.
  • Identifiant de la fiche : 1991-0796
  • Langues : Anglais
  • Date d'édition : 1989
  • Source : Source : ASHRAE Trans.
    vol. 95; n. 2; 1050-1057; 12 fig.; 1 tabl.; 16 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.