INFLUENCE D'UN CYCLE COURT ET DU RETARD DU VENTILATEUR SUR L'EFFICACITE D'UNE POMPE A CHALEUR MODIFIEE POUR IMMEUBLES RESIDENTIELS.

THE EFFECT OF SHORT CYCLING AND FAN DELAY ON THE EFFICIENCY OF A MODIFIED RESIDENTIAL HEAT PUMP.

Auteurs : MULROY W. J.

Résumé

CETTE ETUDE AVAIT POUR OBJET DE DETERMINER SI L'UTILISATION D'UN DISPOSITIF DE REGULATION DU CYCLE AMELIORERAIT LE RENDEMENT D'UN CONDITIONNEUR D'AIR OU D'UNE POMPE A CHALEUR POUR IMMEUBLES RESIDENTIELS. DES ESSAIS CYCLIQUES ONT ETE EFFECTUES DANS TROIS CONFIGURATIONS : SANS MODIFICATION, MODIFIEE POUR SIMULER UN DETENDEUR SANS DEBIT DE FUITE PAR FONCTIONNEMENT D'UN ROBINET SUR LA CONDUITE DE LIQUIDE ET MODIFIEE POUR SIMULER UN CONDITIONNEUR D'AIR PAR SUPPRESSION DE L'ACCUMULATEUR. ON A TROUVE QUE LES DEUX MODIFICATIONS AMELIORAIENT BEAUCOUP LA PERFORMANCE A DES DEGRES A PEU PRES EGAUX ; CEPENDANT IL RESTAIT DES PERTES CYCLIQUES. ON A CONCLU QUE TOUTE STRATEGIE DE REGULATION ENTRAINANT UNE REDUCTION DES TEMPS DE FONCTIONNEMENT DU CYCLE REDUIRAIENT LE RENDEMENT CYCLIQUE POUR TOUS LES TYPES ESSAYES.

Détails

  • Titre original : THE EFFECT OF SHORT CYCLING AND FAN DELAY ON THE EFFICIENCY OF A MODIFIED RESIDENTIAL HEAT PUMP.
  • Identifiant de la fiche : 1987-1142
  • Langues : Anglais
  • Date d'édition : 1986
  • Source : Source : ASHRAE Trans.
    vol. 92; n. 1B; 813-826; 12 fig.; 1 tabl.; 6 ref.; discuss.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.