Influence de la fraction massique du frigorigène sur la performance d'un réfrigérateur à absorption à ammoniac.
Influence of the refrigerant mass fraction in the performance of an ammonia absorption refrigerator.
Auteurs : TAKESHITA K., AMANO Y., HASHIZUME T., et al.
Type d'article : Article
Résumé
The performance of the rectifying column affects the COP of an ammonia absorption refrigerator. The ammonia mass fraction of the refrigerant is one of the key parameters indicating the performance of the rectifying column. The authors propose a method to estimate the refrigerant mass fraction with mass and energy balance equations around the separator at the inlet of the evaporator, and describe the results of experiments which measured the refrigerant mass fraction by sampling from the refrigerant receiver. Throughout these investigations, the refrigerant mass fraction turned out to be lower than the expected value calculated from the condition of dry-saturated vapour at the top of the rectifying column. The refrigerant mass fraction can be estimated within an accuracy of 0.3% by the estimation method based on mass and energy balance equations.
Détails
- Titre original : Influence of the refrigerant mass fraction in the performance of an ammonia absorption refrigerator.
- Identifiant de la fiche : 2005-1839
- Langues : Anglais
- Source : JSME int. J., B - vol. 47 - n. 2
- Date d'édition : 2004
Liens
Voir d'autres articles du même numéro (2)
Voir la source
Indexation
-
Experimental investigation of mass transfer per...
- Auteurs : SIERES J., FERNÁNDEZ-SEARA J.
- Date : 07/2007
- Langues : Anglais
- Source : International Journal of thermal Sciences - vol. 46 - n. 7
Voir la fiche
-
Mass transfer characteristics of a structured p...
- Auteurs : SIERES J., FERNÁNDEZ-SEARA J.
- Date : 01/2007
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 30 - n. 1
- Formats : PDF
Voir la fiche
-
Desorber and rectifier geometries for ammonia-w...
- Auteurs : DELAHANTY J. C., HUGHES M., GARIMELLA S.
- Date : 02/2021
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 122
- Formats : PDF
Voir la fiche
-
Heat and mass transfer analysis of a helical co...
- Auteurs : FERNÁNDEZ-SEARA J., SIERES J., VÁZQUEZ M.
- Date : 08/2003
- Langues : Anglais
- Source : International Journal of thermal Sciences - vol. 42 - n. 8
Voir la fiche
-
Experimental characterization of the rectificat...
- Auteurs : SIERES J., FERNÁNDEZ-SEARA J., UHÍA F. J.
- Date : 09/2009
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 6
- Formats : PDF
Voir la fiche