INFLUENCE DU GIVRAGE ET DU DEGIVRAGE DE L'EVAPORATEUR SUR LA PERFORMANCE DES POMPES A CHALEUR AIR-EAU.

EFFECTS OF EVAPORATOR FROSTING AND DEFROSTING ON THE PERFORMANCE OF AIR-TO-WATER HEAT PUMPS.

Auteurs : TASSOU S. A., MARQUAND C. J.

Type d'article : Article

Résumé

ON ETUDIE LA PERFORMANCE D'UNE POMPE A CHALEUR AIR-EAU DE 8 KILOWATT FONCTIONNANT AVEC GIVRAGE SUR UNE LARGE PLAGE DE TEMPERATURES ET D'HUMIDITES AMBIANTES. LE TAUX DE FORMATION DE GIVRE ET LA DEGRADATION DE LA PERFORMANCE DE LA POMPE A CHALEUR DEPENDENT A LA FOIS DE LA TEMPERATURE ET DE L'HUMIDITE ET ON INDIQUE QU'IL FAUT TENIR COMPTE DE LEURS EFFETS LORSQU'ON CONCOIT DES MECANISMES D'ELIMINATION DU GIVRE. LE DIFFERENTIEL DE PRESSION D'AIR A TRAVERS L'EVAPORATEUR DONNE UNE INDICATION ADEQUATE DE L'IMPORTANCE DE GIVRE ET PEUT ETRE UTILISE POUR FAIRE DEMARRER LE CYCLE DE DEGIVRAGE. UN TEMPS DE DEGIVRAGE DE 5 MIN ETAIT SUFFISANT POUR ELIMINER COMPLETEMENT LE GIVRE DE L'EVAPORATEUR. (INT. BUILD. SERV. ABSTR., GB., 23, N 1, 1988, 8, 88-00066.

Détails

  • Titre original : EFFECTS OF EVAPORATOR FROSTING AND DEFROSTING ON THE PERFORMANCE OF AIR-TO-WATER HEAT PUMPS.
  • Identifiant de la fiche : 1988-2028
  • Langues : Anglais
  • Source : Appl. Energy - vol. 28 - n. 1
  • Date d'édition : 1987
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.