Document IIF

Intégration d’un échangeur de chaleur compact à PCM à deux fluides dans la section chaude surchauffée d’un cycle de pompe à chaleur aérothermique pour la génération optimisée d’eau chaude sanitaire.

Integration of a compact two fluid PCM heat exchanger into the hot superheated section of an air source heat pump cycle for optimized DHW generation.

Numéro : pap. n. 645

Auteurs : EMHOFER J., BARZ T., MARX K., et al.

Résumé

This contribution presents a concept for the direct integration of a refrigerant/water Heat Exchanger (HEX) with a Phase Change Material (PCM) in the hot superheated section of an R32 - air source compression Heat Pump (HP) cycle, for optimized Domestic Hot Water (DHW) generation in multifamily houses. The concept takes advantage of the PCMs high thermal storage capacity integrated into a high performance compact enhanced plate-and-fin aluminium HEX. On the refrigerant side, it works as a de-superheater for DHW generation during heating and cooling operation whereas the process water is connected to decentralized DHW storages located in single apartments of a low energy building. We present results from simulations at a system level for typical operating conditions and corresponding seasonal and annual performances. Compared to conventional systems, the
results indicate savings up to 11% of electric energy over the year for DHW generation in average climate.

Documents disponibles

Format PDF

Pages : 9

Disponible

Gratuit

Détails

  • Titre original : Integration of a compact two fluid PCM heat exchanger into the hot superheated section of an air source heat pump cycle for optimized DHW generation.
  • Identifiant de la fiche : 30026464
  • Langues : Anglais
  • Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Date d'édition : 24/08/2019
  • DOI : http://dx.doi.org/10.18462/iir.icr.2019.0645