Intégration d'un refroidisseur à adsorption dans un système de conditionnement d'air à déshydratant à cycle ouvert.

Integration of an adsorption chiller in an open cycle desiccant assisted air conditioning system.

Numéro : pap. n. 90

Auteurs : SPEERFORCK A., SCHMITZ G.

Résumé

In a pilot installation at Hamburg University of Technology the coupled operation of an open cycle desiccant assisted air conditioning system with an adsorption chiller in combination with cooling ceilings to remove sensible loads is investigated. The paper presents experimental results of the year 2013 with a special focus on the performance of the adsorption chiller. Furthermore, the system is compared to a similar system relying on a vapor compression chiller. The average thermal COP of the adsorption chiller during the investigated period is satisfying (COP th = 0.54), while the average electrical COP does not meet the expectations (COPel = 6.2). The fan control of the dry cooler can be identified as a main cause for the non-satisfying electrical performance. However, depending on the heat supply, up to 29 % of the primary energy demanded by a reference hybrid air conditioning system can be saved by the investigated pilot installation.

Documents disponibles

Format PDF

Pages : 10 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Integration of an adsorption chiller in an open cycle desiccant assisted air conditioning system.
  • Identifiant de la fiche : 30013908
  • Langues : Anglais
  • Source : International sorption heat pump conference (ISHPC2014), College Park, United States, March 31-April 2, 2014.
  • Date d'édition : 02/03/2014

Liens


Voir d'autres communications du même compte rendu (125)
Voir le compte rendu de la conférence