Document IIF
L'analyse de l'effet de la solution de régénération dans un système à déshydratant liquide sur les performances du système par le taux de reflux.
Analysis of the effect on the system performance by the reflux ratio of regeneration solution in liquid desiccant system.
Résumé
In conventional liquid desiccant system, the diluted solution after dehumidification is usually completely sent to the regenerator, which leads to the poor system performance. This paper tries to study on the effect of the solution regeneration reflux ratio on the overall system. Firstly, the novel configuration of liquid desiccant system that can adjust the reflux ratio of regeneration was put forward. Then, the major components of the system were modelled mathematically. Lastly, energy consumption and the system coefficient of performance (COP) under different conditions, including different moisture-removing load and varied solution regeneration reflux ratio, were simulated. The results show that, the overall performance of the liquid desiccant system can be improved by reducing the solution regeneration reflux ratio, moreover, the improving effect are stronger under lower solution regeneration temperature and lower moisture-removing load. However, the reflux ratio cannot be reduced unlimited since the regeneration temperature will be higher, thus there is a rational optimal solution regeneration reflux ratio.
Documents disponibles
Format PDF
Pages : 8 p.
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Analysis of the effect on the system performance by the reflux ratio of regeneration solution in liquid desiccant system.
- Identifiant de la fiche : 30015653
- Langues : Anglais
- Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Date d'édition : 16/08/2015
- DOI : http://dx.doi.org/10.18462/iir.icr.2015.0640
Liens
Voir d'autres communications du même compte rendu (657)
Voir le compte rendu de la conférence
-
Experimental and theoretical research on the cu...
- Auteurs : QING C., SHUN J.
- Date : 12/2018
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 96
- Formats : PDF
Voir la fiche
-
Performance of a four-divided adsorbent rotor f...
- Auteurs : KODAMA A., SANNO A., OSAKA Y.
- Date : 06/04/2011
- Langues : Anglais
- Source : Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Formats : PDF
Voir la fiche
-
Modeling of a flat plate membrane-distillation ...
- Auteurs : RATTNER A. S., NAGAVARAPU A. K., GARIMELLA S., et al.
- Date : 07/2011
- Langues : Anglais
- Source : International Journal of Heat and Mass Transfer - vol. 54 - n. 15-16
Voir la fiche
-
Experimental study on combined low temperature ...
- Auteurs : ARUN B. S., MARIAPPAN V., MAISOTSENKO V.
- Date : 04/2020
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 112
- Formats : PDF
Voir la fiche
-
Improved simulation model for air-liquid contac...
- Auteurs : GOMMED K., GROSSMAN G.
- Date : 02/03/2014
- Langues : Anglais
- Source : International sorption heat pump conference (ISHPC2014), College Park, United States, March 31-April 2, 2014.
- Formats : PDF
Voir la fiche