La conception et l'étude de performances d'un nouveau type de transformateur de chaleur avec absorption, à bromure de lithium-eau.

Conceperea si studiul performantelor unui nou tip de tranformator de caldura cu absorbtie, cu bromura de litiu: apa.

Auteurs : PORNEALA S.

Type d'article : Article

Résumé

The paper presents a two-stage plant which may be used to produce very high temperatures of heat delivered by the absorber. The proposed vapour absorption heat transformers with water-lithium bromide operates at three pressure levels. Heat is rejected at low-pressure condenser to the ambient. Heat is supplied at low-pressure generator and the medium-pressure evaporator. Heat released by the medium-pressure absorber is received at the high-pressure evaporator. The useful heat is delivered at the high-pressure absorber. The paper presents the calculation procedure wtih an original theoretical approach.

Détails

  • Titre original : Conceperea si studiul performantelor unui nou tip de tranformator de caldura cu absorbtie, cu bromura de litiu: apa.
  • Identifiant de la fiche : 1999-2887
  • Langues : Roumain
  • Source : ECO-CLIMA - n. 1-2
  • Date d'édition : 06/1998
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (2)
Voir la source