Document IIF

LA PREMIERE APPLICATION INDUSTRIELLE D'UN MELANGE NON AZEOTROPIQUE.

FIRST INDUSTRIAL APPLICATION OF NON-AZEOTROPIC MIXTURE.

Auteurs : BLAISE J. C., DUTTO T., AMBROSINO J. L.

Type d'article : Article, Article de la RIF

Résumé

DES ESSAIS ONT ETE MENES SUR UNE POMPE A CHALEUR QUI RECUPERE DE L'ENERGIE A PARTIR D'UNE INSTALLATION FRIGORIFIQUE ET QUI CHAUFFE DE L'EAU DE 331 A 341 K (58 A 68 DEG C), AVEC POUR OBJECTIF DE COMPARER LE COP ET LA PUISSANCE THERMIQUE DE LA POMPE A CHALEUR EN UTILISANT UN MELANGE NON AZEOTROPIQUE PLUTOT QUE DU R12. LES AUTEURS FOURNISSENT LES RESULTATS DES ESSAIS QUI MONTRENT L'INTERET DU MELANGE TERNAIRE UTILISE. ILS ONT ETUDIE L'EFFET DES FUITES DE FRIGORIGENE SUR LA COMPOSITION DU MELANGE. CES FUITES, A L'ENTREE DE L'EVAPORATEUR A DETENTE DIRECTE ET A LA PARTIE SUPERIEURE DU RESERVOIR, NE MODIFIENT PAS SUFFISAMMENT LA CONCENTRATION DES DIFFERENTS COMPOSANTS POUR POUVOIR PROVOQUER UNE MODIFICATION DES CONDITIONS DE FONCTIONNEMENT.

Documents disponibles

Format PDF

Pages : 255-258

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : FIRST INDUSTRIAL APPLICATION OF NON-AZEOTROPIC MIXTURE.
  • Identifiant de la fiche : 1991-0827
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 12 - n. 5
  • Date d'édition : 1989

Liens


Voir d'autres articles du même numéro (8)
Voir la source