This paper presents HFC32 boiling heat transfer coefficients measured inside a small Brazed Plate Heat Exchanger (BPHE): the effects of heat flux, saturation temperature (pressure), and outlet conditions are investigated. The experimental tests were carried out at three different saturation temperatures (10, 15, and 20°C) and four different evaporator outlet conditions (vapour quality around 0.80 and 1.00, vapour superheating around 5 and 10°C). The heat transfer coefficients show great sensitivity to heat flux and outlet conditions and weak sensitivity to saturation temperature (pressure). The saturated boiling heat transfer coefficients were compared with a new model for refrigerant vaporisation inside BPHE: the mean absolute percentage deviation between calculated and experimental data is 4.7%. HFC32 exhibits heat transfer coefficients 20-30% lower than those of HFC410A under the same operating conditions.

Documents disponibles

Format PDF

Pages : 9 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : HFC32 vaporisation inside a brazed plate heat exchanger (BPHE).
  • Identifiant de la fiche : 30015776
  • Langues : Anglais
  • Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
  • Date d'édition : 16/08/2015
  • DOI : http://dx.doi.org/10.18462/iir.icr.2015.0190

Liens


Voir d'autres communications du même compte rendu (657)
Voir le compte rendu de la conférence