Les propriétés acoustiques de pléna de chauffage, ventilation et de conditionnement d'air.

The acoustic properties of common HVAC plena.

Résumé

The HVAC plenum is commonly applied as a means to reduce problematic low-frequency noise produced by mechanical equipment in ducted systems. Through the ASHRAE-sponsored research project RP-1026, rigorous testing enabled the identification of comprehensive attenuation properties for common HVAC plena. A two-stage prediction approach resulted, which applies an improved version of the Wells equation for mid- to high-frequency attenuation (5000 Hz upper frequency limit), quantified as a transmission loss, and a surface area and wall characteristic model for the critical low-frequency transmission loss (50 Hz lower frequency limit). This method has improved the prediction accuracy of flow-through type HVAC plena with a volume range of 0.5-30 m3. In addition, this work has identified acoustical effects for seven different wall-lining systems and typical geometric variables, such as opening offsets, opening ratio variables, and multiple openings.

Détails

  • Titre original : The acoustic properties of common HVAC plena.
  • Identifiant de la fiche : 2006-0878
  • Langues : Anglais
  • Source : ASHRAE Transactions. 2004 Annual Meeting, Nashville, Tennessee, USA. Volume 110, part 2 + CD-ROM.
  • Date d'édition : 2004