Document IIF
Localisation des fuites de frigorigène dans une canalisation en cuivre en utilisant les paramètres du nombre de signaux et de la durée dans la technique des émissions acoustiques.
Refrigerant leakage localization in copper pipeline utilizing count-duration features of acoustic emission technique.
Résumé
Leakage detection in pipelines, particularly those transporting refrigerants like R-410A through copper pipes, is critical for maintaining system efficiency and preventing environmental hazards. This study introduces a novel leakage detection and localization method using a single Acoustic Emission (AE) sensor combined with exponential curve fitting to estimate leak locations. Unlike conventional approaches that rely on multiple sensors, this method uses a single sensor but collects data from multiple monitoring points along the pipeline, ensuring high accuracy in leak localization. Although multiple monitoring points are required, this method significantly reduces sensor movement, limiting it to only a few centimeters, which reduces operational complexity and inconvenience. The proposed Count-Duration Ratio parameter enables precise leakage localization, with experimental results showing a maximum error of only 136 mm. The study consists of two stages: threshold calibration to optimize signal detection parameters, followed by an experimental evaluation on a 15-meter copper pipeline to assess the method’s performance across various pipe diameters. The results demonstrate the method’s versatility and effectiveness for copper pipelines, showing promise for enhancing air conditioning system monitoring and maintenance practices in various industries.
Documents disponibles
Format PDF
Pages : 10 p.
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Refrigerant leakage localization in copper pipeline utilizing count-duration features of acoustic emission technique.
- Identifiant de la fiche : 30034454
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 180
- Date d'édition : 12/2025
- DOI : http://dx.doi.org/https://doi.org/10.1016/j.ijrefrig.2025.09.008
Liens
Voir d'autres articles du même numéro (45)
Voir la source
Indexation
- Thèmes : N/A
- Mots-clés : N/A