Mesures de la densité du liquide saturé pour les mélanges HFC-134a/huile.

Measurements of the saturated liquid density for HFC-134a + oil mixtures.

Résumé

The paper reports experimental results of the saturated liquid density for four combinations of HFC-134a and its compatible lubricants such as polyalkyleneglycol (PAG) and polyolester (POE) oils. The saturated liquid density is measured by the method using spherical buoys made of glass. The experiments have been conducted for temperatures from 256 to 313 K, densities from 933 to 1327 kg/m3 and oil concentrations from 0 to 1. The results show that the saturated liquid density for HFC-134a + oil mixtures decreases with increasing oil concentration at a constant temperature while showing slightly positive or negative deviations from the mass fraction average for the experimental temperatures concerned.

Détails

  • Titre original : Measurements of the saturated liquid density for HFC-134a + oil mixtures.
  • Identifiant de la fiche : 2006-1088
  • Langues : Anglais
  • Source : Green breeze from Asia: frontiers of refrigerants, heat transfer and system.. ACRA-2002. Proceedings of the Asian conference on refrigeration and air conditioning.
  • Date d'édition : 04/12/2002

Liens


Voir d'autres communications du même compte rendu (50)
Voir le compte rendu de la conférence