MESURES DE LA QUALITE DE L'AIR DANS UN IMMEUBLE DE BUREAUX CLIMATISE.

INDOOR AIR QUALITY MEASUREMENTS IN AN AIR-CONDITIONED OFFICE BUILDING.

Auteurs : IKEDA K.

Résumé

ON A EFFECTUE DES MESURES DE LA QUALITE DE L'AIR AINSI QUE DES MESURES DU DEBIT D'AIR D'UN SYSTEME DE CONDITIONNEMENT D'AIR DANS UN IMMEUBLE DE BUREAUX. LES CONTAMINANTS MESURES ETAIENT CO2, DES PARTICULES EN SUSPENSION DANS L'AIR, LE MONOXYDE D'AZOTE, LE DIOXYDE D'AZOTE ET DES BACTERIES EN SUSPENSION DANS L'AIR. ON A TROUVE QUE LES NIVEAUX INTERIEURS DE CO2 ET DE PARTICULES EN SUSPENSION ETAIENT TRES ELEVES, 1.600 PPM POUR LE PREMIER ET 0,25 MILLIGRAMMES/M3 POUR LE SECOND. ON A TROUVE QUE LA CAUSE DE CETTE CONCENTRATION ELEVEE ETAIT LES FUITES D'AIR DANS LE CONDUIT D'AMENEE D'AIR NEUF. ON A ESTIME LE TAUX DE FUITE D'AIR EN APPLIQUANT LE MODELE D'EQUILIBRE DE MASSE DE CO2. LES RESULTATS ONT INDIQUE QUE LE TAUX REEL D'AMENEE D'AIR NEUF ETAIT INFERIEUR A LA MOITIE DE CELUI ATTENDU. ON A EXAMINE LA POSSIBILITE D'APPLICATION DU MODELE ET ON CONSIDERE QU'IL ETAIT SATISFAISANT DANS LA PRATIQUE.

Détails

  • Titre original : INDOOR AIR QUALITY MEASUREMENTS IN AN AIR-CONDITIONED OFFICE BUILDING.
  • Identifiant de la fiche : 1987-0682
  • Langues : Anglais
  • Date d'édition : 1986
  • Source : Source : ASHRAE Trans.
    vol. 92; n. 1A; 317-329; 5 fig.; 3 tabl.; 11 ref.; discuss.