Méthode de calcul de la charge thermique basée sur la durée du rayonnement.

The radiant time series cooling load calculation procedure.

Résumé

The radiant time series method is a new method for performing design cooling load calculations, derived from the heat balance method. It effectively replaces all other simplified (non-heat-balance) methods such as the cooling load temperature difference/solar cooling load/cooling load factor method, the total equivalent temperature difference/time averaging method, and the transfer function method. The radiant time series method relies on a 24-term response factor series to compute heat gain, and it relies on a 24-term "radiant time series" to convert instantaneous radiant heat gain to cooling loads. The paper describes the radiant time series method and the generation of the response factors and the radiant time series coefficients and gives a brief comparison to the heat balance method.

Détails

  • Titre original : The radiant time series cooling load calculation procedure.
  • Identifiant de la fiche : 1999-0361
  • Langues : Anglais
  • Source : ASHRAE Transactions.1997 Annual Meeting, Boston, MA.
  • Date d'édition : 1997
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (45)
Voir le compte rendu de la conférence