MODELE AMELIORE POUR LA CONCEPTION DE REFROIDISSEURS D'AIR A TUBES LISSES ET DE BATTERIES DE DESHUMIDIFICATION.

AN IMPROVED MODEL FOR THE DESIGN OF PLAIN TUBE AIR COOLING AND DEHUMIDIFYING COILS.

Résumé

ON PRESENTE UN MODELE POUR LA CONCEPTION DE REFROIDISSEURS D'AIR A TUBES LISSES UTILISES DANS DIVERSES CONDITIONS : MOUILLES, PARTIELLEMENT SECS OU COMPLETEMENT SECS. EN PARTANT DE L'ANALYSE CLASSIQUE DE GOODMAN, LE NOUVEAU MODELE UTILISE DE NOUVELLES CORRELATIONS CONCERNANT LES COEFFICIENTS DE TRANSFERTS DE CHALEUR ET DE MASSE, A L'INTERIEUR DE L'ECHANGEUR DE CHALEUR, AFIN DE PREVOIR LA VARIATION DES ETATS DE L'AIR LE LONG DE SA LONGUEUR, C'EST-A-DIRE D'UNE RANGEE A LA SUIVANTE. AFIN DE VERIFIER LE MODELE, ON A EFFECTUE UN NOMBRE IMPORTANT D'ESSAIS DANS PLUSIEURS CONDITIONS DE DEBITS MASSEE'RE. ON UTILISE ENSUITE LE MODELE POUR ETUDIER L'INFLUENCE DES PARAMETRES DE CONCEPTION DE LA BATTERIE AINSI QUE DES CONDITIONS D'ENTREE DE L'AIR ET DE L'EAU SUR SA PERFORMANCE. UNE COMPARAISON AVEC DES RESULTATS EXPERIMENTAUX MONTRENT QUE LE MODELE EST PLUS PERFORMANT QUE LES PROCEDES UTILISANT LA RELATION DE LEWIS.

Détails

  • Titre original : AN IMPROVED MODEL FOR THE DESIGN OF PLAIN TUBE AIR COOLING AND DEHUMIDIFYING COILS.
  • Identifiant de la fiche : 1989-2265
  • Langues : Anglais
  • Date d'édition : 1988
  • Source : Source : ASHRAE Trans.
    vol. 94; n. 2; 792-812; 12 fig.; 1 tabl.; 13 ref.; append.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.